The National Consumer Commission (NCC) informs consumers about the recall of certain Schneider Electric SYBTU1 and SYBTU2 battery modules used in Symmetra PX, Smart UPS VT and Galaxy 3500 Uninterruptible Power Supply (UPS) systems, as notified by Schneider Electric South Africa.
The affected battery modules can be identified by the following model numbers: SYBTU1-PLP, SYBTHU1-PLP, SYBTU2-PLP and SYBTU2-PLPLL. The affected units have serial numbers starting with “5D” and were made available for sale between September 2024 and October 2025.
According to Schneider Electric, the recall is due to inadequate grounding of the battery module enclosure, which may create an electric shock hazard under fault conditions. A total of 1 308 battery modules is affected. The products were supplied directly to Schneider Electric’s business customers and are used in large industrial and commercial applications.
Customers who own the affected battery modules should check the model and serial numbers, then contact Schneider Electric to arrange an inspection and any necessary corrective action.
Questions relating to this recall may be directed to: ProductRecall@thencc.org.za.